Description
Product Key Feature’s:
Â
Model suits any ceiling format
High EER, low annual power consumption
Low height single fan outdoor units
Cooling operation down to -15°C ambient
R22 replacement technology (3 series outdoor units only)
High CoP, up to record 3.90
Wired remote controller
Slim construction 235mm
Pipe runs up to  20 meters
Low noise 28dBA on low
Cold draft prevention on heat pump start up
Fault diagnosis
Auto re-start after power interruption
PRE-CHARGED WITH REFRIGERANT for up to 20 metres pipe length
Light weight noise absorbing outdoor unit
Technical Specification:
Model Reference RAV-SM567CTP-EÂ
Nominal Cooling (kW) 5.0Â
Nominal Heating (kW) 5.3Â
Annual Power ConsumptionÂ
(SM / SP *) (kWh)Â 805 / 780Â
UK Cooling (SM / SP*Â ) (kW) 4.7 / 4.7Â
UK Sensible Cooling (SM / SP*Â ) (kW) 3.4 / 3.4Â
UK Heating (SM / SP*Â ) (kW) 4.53 / 5.18Â
Starting Current (SM / SP*) (A) 1 / 1Â
Running Current (SM / SP *) (A) 7.75 / 7.24Â
Suggested Fuse Size (SM / SP *) (A) 16 / 16Â
Power Supply (V-ph-Hz) 220/240-1-50Â
Interconnecting Cable 3 core plus earthÂ
Sound Power H-L (dB(A)) 52-43Â
Sound Pressure H-L (dB(A)) 43-34Â
Air Flow H-L (m3/h) 798-546Â
Air Flow H-L (l/s) 221-151Â
Dimensions (HxWxD) (mm) 235 x 950 x 690Â
Unit Weight (kg) 23Â
Energy Label Cool/Heat (SM / SP*) A
EER / COP (SM / SP*Â ) 3.11/3.48 3.21/3.64Â
SEER / SCOP (SM / SP*) 5.48/4.16 5.61/4.20Â
Pipe Sizes (Liquid / Suction) (Inch) 1/4—1/2Â



Reviews