Description
Technical Information:
Lg Air Conditioning Standard Plus PC12SK-NSJ
| Cooling | Min. / Rated / Max. | kW | 0.89 / 3.50 / 4.04 | |
| Capacity | Heating | Min. / Rated / Max. | kW | 0.89 / 4.00 / 5.10 |
| Heating -7°C | Rated | kW | 3.00 | |
| Power Input | Cooling / Heating | Rated | W | 1,080 / 1,050 |
| EER | W/W | 3.24 | ||
| S.E.E.R. | 6.60 | |||
| P design C | kW | 3.50 | ||
| COP | W/W | 3.81 | ||
| S.C.O.P | (Average / Warmer) | 4.00 / 4.90 | ||
| P design H (Average / Warmer) | kW | 2.50 / 1.30 | ||
| Energy Label | Cooling | A++ | ||
| (A+++ to D Scale) | Heating | (Average / Warmer) | A+ / A++ | |
| A n n u a l E n e r g y | Cooling | kWh | 186 | |
| Consumption | Heating | (Average / Warmer) | kWh | 875 / 371 |
| Cooling | S / L / M / H | dB(A) | 19 / 27 / 35 / 41 | |
| Heating | L / M / H | dB(A) | 27 / 35 / 41 | |
| Sound Power | Cooling | dB(A) | 59 | |
| Air Flow Rate Dehumidification Rate | Cooling | S / L / M / H / Max. (Power) | m3/min | 3.0 / 4.2 / 7.5 / 10.0 / 12.5 |
| Heating | L / M / H m3/min | 5.6 / 7.2 / 10.0 | ||
| l/h | 1.3 | |||
| Cooling | Min. / Rated / Max. A | 1.10 / 4.70 / 6.00 | ||
| Heating | Min. / Rated / Max.A | 1.10 / 4.70 / 7.00 | ||
| Starting Current | Cooling / Heating | Rated A | 4.70 / 4.70 | |
Technical Specifications Outdoor Multi:
| OUTDOOR UNIT | |||
| Compressor Type | Twin Rotary | ||
| Capacity * | Cooling | Min / Nom / Max kW | 1.3 / 7.0 / 8.5 |
| Heating | Min / Nom / Max kW | 1.5 / 8.4 / 9.4 | |
| Low Temperature Capacity Heating -7°C | Max kW | 5.9 | |
| Power Input * | Cooling | Min / Nom / Max kW | 0.4 / 1.5 / 2.6 |
| Heating | Min / Nom / Max kW | 0.6 / 1.8 / 2.9 | |
| Running Current | Cooling | Min / Nom / Max A | 1.9 / 6.6 / 11.9 |
| Heating | Min / Nom / Max A | 2.8 / 8.3 / 13.1 | |
| EER | 4.82 | ||
| COP | 4.61 | ||
| SEER | 8.20 | ||
| SCOP | 4.20 | ||
| Pdesign (@-10°C) | kW | 7.00 | |
| Seasonal Energy Label Cooling / Heating | A++ / A+ | ||
| Annual Energy Consumption Cooling / Heating | 299 / 2,333 | ||
| Airflow Rate Nom | m3/min | 60 | |
| Sound Pressure | Cooling | Nom dBA | 49 |
| Heating | Nom dBA | 53 | |
| Sound Power Cooling | Max dBA | 64 | |
| Dimensions W x H x D mm | 950 x 834 x 330 | ||
| Net Weight | Kg | 61 | |
| Refrigerant | Type | R32 | |
| Charge Kg | 2.3 | ||
| Additional Charge g/m | 20 | ||
| GWP | 675 675 675 | ||
| t-CO2 eq | 1.55 1.55 1.76 | ||
| Operation Range (Outdoor) | Cooling | Min ~ Max °C DB | -10 ~ 48 |
| Heating | Min ~ Max °C WB | -18 ~ 18 | |
| Power Supply | Ø / V / Hz | 1 / 220-240 / 50 | |
| Power Supply Cable | No. x mm2 | 3C x 2.5 | |
| Transmission Cable | No. x mm2 | 4C x 0.75 | |
| Circuit Breaker | A | 25 | |
| Piping Length Total | m | 70 | |
| Piping Length per Branch | Max m | 25 | |
| Piping Elevation Difference | IDU – ODU | Max m | 15 |
| IDU – IDU | Max m | 7.5 | |
| Piping Connections | Liquid mm(inch) x No. | Ø6.35 (1/4) x 4 | |
| Gas mm(inch) x No. | Ø9.52 (3/8) x 4 | ||
These air conditioning units must be installed by an F-Gas qualified engineer. ( We will ask to view this certificate before the shipment) We can install the unit for you using our F-Gas Certified Engineers


Reviews