Description
Technical Information:
Lg Air Conditioning Standard Plus PC18SK-NSK
UNIT INDOOR | 18K | |
0.90 / 5.00 / 5.50 | ||
Capacity | Cooling Min. / Rated / Max. kW | |
Heating Min. / Rated / Max. kW | 0.90 / 5.80 / 6.40 | |
Heating -7°C Rated kW | 4.20 | |
Power Input Cooling / Heating Rated W | 1,562 / 1,611 | |
EER W/W | 3.20 | |
S.E.E.R. | 7.00 | |
P design C kW | 5.00 | |
COP W/W | 3.60 | |
S.C.O.P (Average / Warmer) | 4.30 / 5.30 | |
P design H (Average / Warmer) kW | 3.90 / 2.10 | |
Energy Label (A+++ to D Scale) | Cooling | A++ |
Heating (Average / Warmer) | A+ / A+++ | |
A n n u a l E n e r g y Consumption | Cooling kWh | 250 |
Heating (Average / Warmer) kWh | 1,270 / 555 | |
Sound Pressure | Cooling S / L / M / H dB(A) | 31 / 34 / 39 / 44 |
Heating L / M / H dB(A) | 34 / 39 / 44 | |
Sound Power Cooling dB(A) | 60 | |
Air Flow Rate | Cooling S / L / M / H / Max. (Power) m3/min | 8.0 / 10.5 / 13.0 / 14.5/ 15.5 |
Heating L / M / H m3/min | 11.0 / 13.5 / 16.0 | |
Dehumidification Rate l/h | 1.8 | |
Running Current | Cooling Min. / Rated / Max. A | 1.20 / 6.90 / 9.00 |
Heating Min. / Rated / Max. A | 1.20 / 7.10 / 9.50 | |
Starting Current Cooling / Heating Rated A | 6.90 / 7.10 | |
Power Supply Ø/ V/ Hz | 1 / 220-240 / 50 | |
Circuit Breaker A | 20 | |
Power Supply Cable N xmm2 | 3 x 1.5 | |
Power & Transmission Cable N xmm2 | 4 x 1.0(Including Earth) | |
Dimension mm | 998 x 345 x 210 | |
Net Weight kg | 11.9 | |
Fan Motor Output W | 30 |
Lg Air Conditioning Standard Plus PC12SK-NSJ
Cooling | Min. / Rated / Max. | kW | 0.89 / 3.50 / 4.04 | |
Capacity | Heating | Min. / Rated / Max. | kW | 0.89 / 4.00 / 5.10 |
Heating -7°C | Rated | kW | 3.00 | |
Power Input | Cooling / Heating | Rated | W | 1,080 / 1,050 |
EER | W/W | 3.24 | ||
S.E.E.R. | 6.60 | |||
P design C | kW | 3.50 | ||
COP | W/W | 3.81 | ||
S.C.O.P | (Average / Warmer) | 4.00 / 4.90 | ||
P design H (Average / Warmer) | kW | 2.50 / 1.30 | ||
Energy Label | Cooling | A++ | ||
(A+++ to D Scale) | Heating | (Average / Warmer) | A+ / A++ | |
A n n u a l E n e r g y | Cooling | kWh | 186 | |
Consumption | Heating | (Average / Warmer) | kWh | 875 / 371 |
Cooling | S / L / M / H | dB(A) | 19 / 27 / 35 / 41 | |
Heating | L / M / H | dB(A) | 27 / 35 / 41 | |
Sound Power | Cooling | dB(A) | 59 | |
Air Flow Rate Dehumidification Rate | Cooling | S / L / M / H / Max. (Power) | m3/min | 3.0 / 4.2 / 7.5 / 10.0 / 12.5 |
Heating | L / M / H m3/min | 5.6 / 7.2 / 10.0 | ||
l/h | 1.3 | |||
Cooling | Min. / Rated / Max. A | 1.10 / 4.70 / 6.00 | ||
Heating | Min. / Rated / Max.A | 1.10 / 4.70 / 7.00 | ||
Starting Current | Cooling / Heating | Rated A | 4.70 / 4.70 |
Technical Specifications Outdoor Multi:
OUTDOOR UNIT | |||
Compressor Type | Twin Rotary | ||
Capacity * | Cooling | Min / Nom / Max kW | 1.3 / 7.0 / 8.5 |
Heating | Min / Nom / Max kW | 1.5 / 8.4 / 9.4 | |
Low Temperature Capacity Heating -7°C | Max kW | 5.9 | |
Power Input * | Cooling | Min / Nom / Max kW | 0.4 / 1.5 / 2.6 |
Heating | Min / Nom / Max kW | 0.6 / 1.8 / 2.9 | |
Running Current | Cooling | Min / Nom / Max A | 1.9 / 6.6 / 11.9 |
Heating | Min / Nom / Max A | 2.8 / 8.3 / 13.1 | |
EER | 4.82 | ||
COP | 4.61 | ||
SEER | 8.20 | ||
SCOP | 4.20 | ||
Pdesign (@-10°C) | kW | 7.00 | |
Seasonal Energy Label Cooling / Heating | A++ / A+ | ||
Annual Energy Consumption Cooling / Heating | 299 / 2,333 | ||
Airflow Rate Nom | m3/min | 60 | |
Sound Pressure | Cooling | Nom dBA | 49 |
Heating | Nom dBA | 53 | |
Sound Power Cooling | Max dBA | 64 | |
Dimensions W x H x D mm | 950 x 834 x 330 | ||
Net Weight | Kg | 61 | |
Refrigerant | Type | R32 | |
Charge Kg | 2.3 | ||
Additional Charge g/m | 20 | ||
GWP | 675 675 675 | ||
t-CO2 eq | 1.55 1.55 1.76 | ||
Operation Range (Outdoor) | Cooling | Min ~ Max °C DB | -10 ~ 48 |
Heating | Min ~ Max °C WB | -18 ~ 18 | |
Power Supply | Ø / V / Hz | 1 / 220-240 / 50 | |
Power Supply Cable | No. x mm2 | 3C x 2.5 | |
Transmission Cable | No. x mm2 | 4C x 0.75 | |
Circuit Breaker | A | 25 | |
Piping Length Total | m | 70 | |
Piping Length per Branch | Max m | 25 | |
Piping Elevation Difference | IDU – ODU | Max m | 15 |
IDU – IDU | Max m | 7.5 | |
Piping Connections | Liquid mm(inch) x No. | Ø6.35 (1/4) x 4 | |
Gas mm(inch) x No. | Ø9.52 (3/8) x 4 |