Description
Technical Specifications:
| Indoor Unit Model | rak-18ped | ||
| Nominal Cooling Capacity (min – max) | kW | 2.00 (0.90 – 2.50) | |
| Sensible Cooling Capacity | kW | 1.99 | |
| UK Cooling Capacity (sensible) | kW | 1.9 (1.7) | |
| Heating capacity at -7°C | kW | 1.75 | |
| Nominal Heating Capacity (min – max) | kW | 2.50 (0.90 – 3.20) | |
| Nominal cooling power input (min – max) | kW | 0.58(0.25-1.01) | |
| Nominal heating power input (min – max) | kW | 0.62(0.25-0.97) | |
| Seasonal Efficiency SEER (4)Energy Efficiency Class Annual Energy Consumption | kWh/yr | 5.80 | |
| A+ | |||
| 121 | |||
| Seasonal Efficiency SCOP (4) (Average Climate)Energy Efficiency Class Annual Energy Consumption | kWh/yr | 3.80 | |
| A | |||
| 316 | |||
| Nominal Load Efficiency EER / COP (5)Energy Class (Cool/Heat) | 3.45/4.03 | ||
| A/A | |||
| Noise level cooling (sound pressure) (SL / L / M / H) | (2) | dB(A) | 21/24/33/37 |
| Noise level heating (sound pressure) (SL / L / M / H) | (2) | dB(A) | 19/22/33/38 |
| Noise level (sound power) (1) | dB(A) | 51 | |
| Air flow cooling mode (SL / L / M / H) | m3/h | 312/350/400/440 | |
| Air flow heating mode (SL / L / M / H) | m 3/h | 312/350/420/480 | |
| Dehumidification | l/h | 1.2 | |
| Dimensions (H x W x D) | mm | 280x780x218 | |
| Weight | kg | 7.5 | |
| Power supply | From Outdoor Unit | ||
| Drain diameter (ext) | φ16mm | ||
| Remote Control | Std | Infra Red (RAR-5F1) | |
| Opt. 1 | Wired (SPX-RCDB) | ||
| Opt. 2 | Wired (SPX-WKT2) | ||
| Outdoor Unit Model | rac-18wed | ||
| Noise level cooling (sound pressure) (night mode) | (3) | dB(A) | 45 |
| Noise level heating (sound pressure) (night mode) | (3) | dB(A) | 46 |
| Noise level (sound power) (1) | dB(A) | 59 | |
| Air flow (Cooling / Heating) | m3/h | 1860/1620 | |
| Dimensions (H x W x D) | mm | 530x660x278 | |
| Weight | kg | 24.5 | |
| Piping diameter (Liquid / Gas) | Inch | 1/4 – 3/8 | |
| mm | 6.35 – 9.52 | ||
| Minimum Piping Length | m | 3.0 | |
| Maximum Piping L | m | 20/10 | |
| Current Quantity of Refrigerant | kg | 0.72 | |
| Chargeless / Additional Refrigerant Charge | m / g/m | 20/ – | |
| Power supply | 230V/1Ph/50Hz | ||
| Recommended fuse size | A | 16 | |
| Starting current (cooling/heating) | A | <1 Amp | |
| Running current (cooling/heating) | A | 1.09-4.39/1.09-4.22 | |
| Interconnecting Cables | No. | 3 + E | |
| Working Range (cooling/heating) | °C | -10°C~+43°C / -15°C~+21°C | |
| Refrigerant / GWP | R32 / 1975 | ||
| Compressor type | Rotary | ||
These air conditioning units must be installed by an F-Gas qualified engineer. ( We will ask to view this certificate before the shipment) We can install the unit for you using our F-Gas Certified Engineers.