Description
TECNICAL SPECIFICATION
Indoor Unit:
Model No. Indoor unit ASYG09KGTB | ||||
kW Class | kW | 2.5 | ||
Power Source | Single phase, ~230V, 50Hz | |||
Sound Pressure Level | Cooling | H/M/L/Q | dB(A) | 40/34/29/21 |
Heating | 42/36/31/22 | |||
Sound Power Level | Cooling | H | dB(A) | 55 |
Heating | 57 | |||
$LUÁRZ 5DWH | Cooling | H/M/L/Q | m3/h | 700/560/430/270 |
Heating | 750/610/470/330 | |||
Net Dimensions | mm | 270x834x215 | ||
Weight | kg(lbs) | 10 (22) | ||
Connection Pipe Diameter | Liquid/Gas | mm | 6.35/9.52 |
Outdoor Unit:
Model No. AOYG14KBTA2 | ||||
Power Source | Single phase, ~230V, 50Hz | |||
Nominal Capacity (min-max) | Cooling | kW | 4.0 (1.4-4.6) | |
Heating | 4.4 (1.1-5.5) | |||
Power consumption | Cooling / Heating | kW | ||
EER | Cooling | W/W | 4.12 | |
COP | Heating | 4.63 | ||
P-design | Cooling/Heating(-10°C) | kW | 4.0 / 3.5 | |
SEER | Cooling | W/W | 8.70 | |
SCOP | Heating (Average) | 4.70 | ||
(ENERGY CLASS) | Cooling | A+++ | ||
Heating (Average) | A++ | |||
Annual Energy Consumption | Cooling | kWh/a | 209 | |
Heating | 1296 | |||
Sound Pressure Level (High) | Cooling | dB(A) | 47 | |
Heating | 49 | |||
Sound Power Level (High) | Cooling | 60 | ||
Heating | 62 | |||
AIR FLOW | Cooling/Heating | m3/h | 1,670/1,670 | |
Net Dimensions H × W × D | mm | 542×799×290 | ||
Weight | kg(lbs) | 33 (73) | ||
Interconnecting Cable (Suggested cable size 1.5mm) | 3 core + earth | |||
Suggested MCB Size | Amp | 15 | ||
Max. Operating Current | Cooling/Heating | Amp | 10.9 | |
Starting Current | Amp | 4.7 | ||
Power Supply To | Outdoor unit | |||
Connection Pipe Diameter | Gas | Inch | 3/8 × 2 | |
Liquid | 1/4×2 | |||
Max. Pipe Length | Total / Each | m | 30 / 20 | |
Max. Height Difference | Between Outdoor Unit and Each Indoor Units. | 15 | ||
Between Indoor Units. | 10 | |||
Refrigerant | Type | R32 | ||
Charge | g | 900 | ||
Additional Charge | g/m | 20 | ||
Operation Range | Cooling | °CDB | -10 to 46 | |
Heating | -15 to 24 |
These air conditioning units must be installed by an F-Gas qualified engineer. ( We will ask to view this certificate before the shipment) We can install the unit for you using our F-Gas Certified Engineers.
Reviews
There are no reviews yet.